Show simple item record

dc.contributor.authorFerguson, Jeffery Don
dc.date.accessioned2014-09-29T19:39:45Z
dc.date.available2014-09-29T19:39:45Z
dc.date.issued1997-05-01
dc.identifier.urihttps://hdl.handle.net/11244/12243
dc.description.abstractThe purpose of this work was to design, build, and validate an experimental room for the study of building interior convective heat transfer. The full-scale room with interior dimensions 16'x12'x1 0', was constructed with 18" walls and 15" floor and ceiling. The facility was elevated 5' above the lab floor and the walls were heavily insulated. All six surfaces were divided into 2'x4' cells with a unique modular heated panel system mounted on the inside of the cells. ASHRAE Standard 51 was employed for volumetric air flow measurement. A water source heat pump provided chilled water to a fan-coil unit which in tum provided conditioned air to the room. A total of seventeen validation tests were performed focusing on volumetric air flow measurement and an overall room heat balance. Analysis was directed at results from a subset of seven experiments ranging from 5-25 ach. Additionally, an uncertainty analysis was performed for all experiments. For the lower volumetric experiments (<10 ach), initial room heat balance results, coupled with the uncertainty results, fell short of good agreement. Further analysis isolated uncertainty sources at the room inlet temperature measurement, radiative communication with room inlet temperature measurement, room conduction backlosses and room transient effects. Recommendations are given to alleviate these uncertainties. Suggestions for future work and research, that the experimental facility could support, are given. The room, while operational, will require further testing, modification and evaluation to be considered a viable building interior convective heat transfer investigative facility.
dc.formatapplication/pdf
dc.languageen_US
dc.publisherOklahoma State University
dc.rightsCopyright is held by the author who has granted the Oklahoma State University Library the non-exclusive right to share this material in its institutional repository. Contact Digital Library Services at lib-dls@okstate.edu or 405-744-9161 for the permission policy on the use, reproduction or distribution of this material.
dc.titleFull Scale Room for the Experimental Study of Interior Building Convective Heat Transfer: Design and Validation
dc.typetext
osu.filenameThesis-1997-F352f.pdf
osu.accesstypeOpen Access
dc.type.genreThesis


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record