Show simple item record

dc.contributor.advisorBach, Christian K.
dc.contributor.authorIstaque, Farhan
dc.date.accessioned2023-08-25T20:06:08Z
dc.date.available2023-08-25T20:06:08Z
dc.date.issued2023-05
dc.identifier.urihttps://hdl.handle.net/11244/338926
dc.description.abstractOne of the major problems with using renewable energy is the mismatch between power generation and demand as renewable energy generation and energy usage from HVAC equipment depend on unsynchronized natural factors. To reduce this supply-demand mismatch many researchers suggested using thermal energy storage to shift cooling and/or heating loads. A thermal energy storage (TES) tank can be integrated with building heating and cooling systems using several methods described in the open literature. This thesis explores a novel method to integrate water-based TES with an indoor air coil using a three fluid heat exchanger (TriCoil(TM)). The three fluid heat exchanger will thermally connect water from the TES, refrigerant from the outdoor unit, and indoor air. A test setup has been developed inside the Psychrometric Coil Testing Facility of Oklahoma State University (OSU) to test the TriCoil(TM). The heat balance of the test setup for different operation modes and test points was within +/-5%. An uncertainty analysis has been performed on the test results and major sources of uncertainties have been identified. In the experiment done for this thesis, water from the TES was successfully charged up to 15 kW (cooling) with a log mean temperature difference (LMTD) of 18.5 K using a 4-ton capacity outdoor unit. TriCoil(TM) was also used to discharge the water from TES with a max capacity of 11.5 kW (heating) with an LMTD of 8.7 K, a water flow rate of 1700 kg/h, and an airflow rate of 1600 CFM.
dc.formatapplication/pdf
dc.languageen_US
dc.rightsCopyright is held by the author who has granted the Oklahoma State University Library the non-exclusive right to share this material in its institutional repository. Contact Digital Library Services at lib-dls@okstate.edu or 405-744-9161 for the permission policy on the use, reproduction or distribution of this material.
dc.titleDevelopment and commissioning of a variable capacity experimental infrastructure for a novel three fluid heat exchanger
dc.contributor.committeeMemberBradshaw, Craig R.
dc.contributor.committeeMemberSpitler, Jeffrey D.
osu.filenameISTIAQUE_okstate_0664M_18162.pdf
osu.accesstypeOpen Access
dc.type.genreThesis
dc.type.materialText
dc.subject.keywordscharging
dc.subject.keywordscross fin conduction
dc.subject.keywordsHVAC
dc.subject.keywordsrenewable energy
dc.subject.keywordsthermal energy storage
dc.subject.keywordsthree fluid heat exchanger
thesis.degree.disciplineMechanical and Aerospace Engineering
thesis.degree.grantorOklahoma State University


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record