Show simple item record

dc.contributor.authorViviescas, Geoffrey
dc.contributor.authorBernier, Michel
dc.contributor.otherIGSHPA Research Track (2022)
dc.date.accessioned2022-12-04T22:08:24Z
dc.date.available2022-12-04T22:08:24Z
dc.date.issued2022
dc.identifieroksd_igshpa_2022_viviescas
dc.identifier.urihttps://hdl.handle.net/11244/336850
dc.description.abstractThe objective of this paper is to compare the required length and performance of ground heat exchangers as well as heat pump energy consumption for fixed and variable speed ground-source heat pumps. In the first part of the paper, a physics-based model of a water-to-water heat pump is briefly presented. This model is incorporated in TRNSYS simulations using a performance map where variable speed operation is handled through a linear relationship linking the COP to the percentage of the full capacity being used. The ground heat exchanger is modeled using a thermal resistance and capacitance approach to account for borehole thermal capacity. Simulations are performed on a typical residential building located in a cold climate (Montreal, Canada) and equipped with either a fixed or variable speed ground-source heat pump. Results are obtained for eight cases with: variable or fixed speed operation (VSC or FSC), with or without consideration of borehole thermal capacity (TC or NTC), and with annual heating needs covered at 90% or 100% by the heat pump. The differences in the required borehole length between the TC and NTC cases are relatively small. The smallest required borehole length is for the FSC-90%-TC case (180 m) and the longest is for the VSC-100%-TC case (250 m). The VSC-100% case has the largest seasonal Performance factor (SPF) at 4.14 and the FSC-90% case has the lowest at 3.11.
dc.formatapplication/pdf
dc.languageen_USen_US
dc.publisherInternational Ground Source Heat Pump Association
dc.rightsIn the Oklahoma State University Library's institutional repository this paper is made available through the open access principles and the terms of agreement/consent between the author(s) and the publisher. The permission policy on the use, reproduction or distribution of the article falls under fair use for educational, scholarship, and research purposes. Contact Digital Resources and Discovery Services at lib-dls@okstate.edu or 405-744-9161 for further information.
dc.titleGround heat exchanger performance with variable speed ground-source heat pumps
osu.filenameoksd_igshpa_2022_viviescas.pdf
dc.identifier.doi10.22488/okstate.22.000029
dc.type.genreConference proceedings
dc.type.materialText


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record