Show simple item record

dc.contributor.authorSpitler, Jeffrey D.
dc.contributor.authorGehlin, Signhild
dc.date.accessioned2021-07-06T21:28:47Z
dc.date.available2021-07-06T21:28:47Z
dc.date.issued2021-04
dc.identifieroksd_spitler_threeyearsperformance_2021
dc.identifier.citationSpitler, J. D., & Gehlin, S. (2021, April 26-29). Three years’ performance monitoring of a mixed-use ground source heat pump system in Stockholm. Paper presented at the thirteenth IEA Heat Pump Conference, Jeju, South Korea.
dc.identifier.urihttps://hdl.handle.net/11244/330125
dc.description.abstractThe student center, Studenthuset, at Stockholm University in Stockholm, completed in the fall of 2013, is a thoroughly instrumented mixed-use 6300 m2 four-story building. Space heating and hot water are provided by a ground source heat pump (GSHP) system consisting of five 40 kW off-the-shelf water-to-water heat pumps connected to 20 boreholes in hard rock, drilled to a depth of 200 m. Space cooling is provided by direct cooling from the boreholes. The Studenthuset building monitoring project is part of the IEA HPT Annex 52 – Long-term performance measurement of GSHP systems serving commercial, institutional and multi-family buildings. This paper presents results from three years of measured performance data to calculate the long-term performance of the Studenthuset GSHP system. A number of performance indices are calculated and presented to describe the short-term and long-term system performance for selected system boundaries. Seasonal, monthly and binned performance coefficients for both heating and cooling operation are presented and discussed. The Legionella protection system, hot water continuous circulation system, and internal heating/cooling distribution system reduce the system energy performance.
dc.formatapplication/pdf
dc.languageen_US
dc.publisherIEA Heat Pump Conference
dc.rightsThis material has been previously published. In the Oklahoma State University Library's institutional repository this version is made available through the open access principles and the terms of agreement/consent between the author(s) and the publisher. The permission policy on the use, reproduction or distribution of the material falls under fair use for educational, scholarship, and research purposes. Contact Digital Resources and Discovery Services at lib-dls@okstate.edu or 405-744-9161 for further information.
dc.titleThree years’ performance monitoring of a mixed-use ground source heat pump system in Stockholm
osu.filenameoksd_spitler_threeyearsperformance_2021.pdf
dc.description.peerreviewPeer reviewed
dc.description.departmentMechanical and Aerospace Engineering
dc.type.genreArticle
dc.type.materialText
dc.subject.keywordsground source heat pumps
dc.subject.keywordsperformance monitoring
dc.subject.keywordscop
dc.subject.keywordsspf
dc.subject.keywordssystem effects
osu.authorOrcid.urihttps://orcid.org/0000-0003-0826-0512


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record